Spec Guide · CSI 26 05 33
Specifying Stainless Steel Conduit: Robroy Stainless
In food, beverage and pharmaceutical facilities, the raceway has to survive daily washdown and stay cleanable. Stainless conduit does both. Here's how to write it into your spec.
When to specify it
Stainless earns its cost where corrosion and contamination risk overlap.
Food and beverage processing
Washdown areas where the raceway is cleaned with water and chemicals on a schedule.
Pharmaceutical and life sciences
Production and clean areas where surfaces need to stay cleanable and corrosion-free.
Harsh corrosive environments
Areas where coated systems could be damaged in service and bare metal has to hold up on its own.
Visible, exposed runs
Spaces where the raceway is part of the finished environment.
What sets Robroy Stainless apart
From Robroy's published Robroy Stainless materials:
- Complies with UL 6A and ANSI C80.5.
- Two product families: Traditional for the harshest corrosive environments, Hygienic for corrosive environments with sanitary concerns.
- Complete system: conduit, elbows, couplings, fittings, boxes, accessories and a sanitary support system.
- Manufactured in the U.S.A. in an ISO 9001:2015 certified operation.
- Robroy positions the line around food safety, corrosion prevention and contamination prevention.
Codes and standards to reference
| Reference | What it covers |
|---|---|
| UL 6A | Electrical rigid metal conduit: aluminum, red brass and stainless steel |
| ANSI C80.5 | Rigid conduit standard Robroy cites for its stainless conduit |
| NEC Article 344 | Rigid metal conduit installation |
What to put in your spec
Write the whole raceway system, not just the pipe.
- Grade: name the stainless grade your process requires and require it on every component.
- Standards: UL 6A listed and ANSI C80.5 compliant conduit.
- System: fittings, elbows, boxes and supports in stainless, so no carbon steel component becomes the weak point.
- Sanitary areas: call for the hygienic product family and a sanitary support system where cleanability matters.
- Domestic content: if the project carries Buy American or domestic-content language, say so in the spec.
Check these at submittal
Mixed-material systems are the most common shortcut. Before you approve:
- The grade on the product data matches the grade you specified.
- Supports, straps and hardware are stainless, not plated steel.
- Fittings and boxes are part of the same stainless system.
- UL 6A listing is shown for the conduit.
- Hygienic products are submitted where you called for them.
- Country of manufacture is documented if domestic content applies.
Resources
Want a second set of eyes on your spec?
Send us your draft section or project details. Our specifications team will review it and send back notes.