Spec Guide · CSI 26 05 33 · 26 05 43 · 27 05 43

Specifying Fiberglass Conduit: Champion Fiberglass

Fiberglass (RTRC) conduit doesn't rust, doesn't conduct, and weighs a fraction of steel. That makes it a strong fit for wastewater, data centers, utilities, tunnels and coastal work. Here's how to specify it.

CSI sections26 05 33 · 26 05 43 · 27 05 43
ListingUL 2515 (above ground)
Brazill coverageNYPHILLYDC

When to specify it

Champion lists wastewater, port and coastal, data centers, petrochemical, tunnels, transportation, utilities and pipeline among its core markets.

Corrosive above-ground runs

Treatment plants, chemical areas and coastal structures, including under-bridge work.

Data centers and utilities

Duct banks and long sweeps, where the elbows' low friction helps keep cable from burning through on long pulls.

Hazardous and high-impact areas

Champion Haz Duct XW for high-impact areas and Class I, Division 2 locations.

Transit tunnels and stations

Champion Flame Shield phenolic conduit, rated 2-hour fire resistant.

What sets Champion apart

From Champion's published materials:

  • UL 2515 listed for above-ground use and marked UL 2515 AG; also marked to NEMA TC 14.
  • UL Listed extended support spans of 10 to 17 ft for 3/4 in. to 6 in. on several Champion Duct and Haz Duct diameters.
  • Weighs up to 1/5 of comparably sized steel conduit.
  • Non-conductive: grounding bushings and exothermic grounding aren't needed for protection during a cable fault.
  • Holds its mechanical properties down to -60°F (elbows).
  • Listed in Product MasterSpec under 26 05 33, 26 05 43 and 27 05 43.

Codes and standards to reference

ReferenceWhat it covers
NEC Article 355Reinforced thermosetting resin conduit (RTRC)
UL 2515Above-ground RTRC and fittings
NEMA TC 14RTRC and fittings

What to put in your spec

Champion's guide specifications are available in Product MasterSpec and on its data sheets page.

  1. Product type: RTRC conduit and elbows by wall type (standard, heavy wall or XW) to match exposure and impact risk.
  2. Listings: UL 2515 for above-ground runs and NEMA TC 14.
  3. Support spacing: reference the manufacturer's UL Listed spans where you're relying on extended spacing, not NEC default spacing.
  4. Elbows: fiberglass elbows on long or heavy pulls to limit cable burn-through.
  5. Supports: fiberglass strut and hangers in corrosive areas, so the support system matches the raceway.
  6. Hazardous locations: Haz Duct XW where the area classification calls for it.

Check these at submittal

Fiberglass products are not interchangeable. Before you approve:

  • Above-ground conduit is marked UL 2515 AG.
  • Wall type matches what you specified for each area.
  • Support spacing in the shop drawings matches the listed spans for those diameters.
  • Elbows are fiberglass where you specified them.
  • Supports are corrosion-resistant, not plain steel.
  • Haz Duct XW is submitted where the area is classified.

Want a second set of eyes on your spec?

Send us your draft section or project details. Our specifications team will review it and send back notes.

Product information is drawn from the manufacturer's published materials. Always confirm current listings and specifications with the manufacturer before issuing documents. Sources: Above-ground applications · Champion Elbows · Utility Solutions Guide · Product MasterSpec listing