Spec Guide · Fire-Rated Circuits

Specifying 2-Hour Fire-Rated Cable: Chemelex Pyrotenax MI

Some circuits have to keep running during a fire: fire pumps, emergency power, alarms, emergency elevators. Pyrotenax mineral insulated (MI) cable is a 2-hour fire-rated wiring system built for exactly that. Here's how to specify it.

CableMineral insulated, copper sheath
Fire testUL 2196 · ULC-S139
Brazill coverageNYPHILLYDC VA STATEWIDE

When to specify it

Chemelex describes these as typical uses for 2-hour fire-rated cable:

Fire pump feeders

Electric fire pump feeds that must stay energized during a fire.

Emergency systems

Emergency generators, emergency lighting and alarm circuits.

Life-safety HVAC and elevators

Air handlers for smoke control and emergency elevator feeds.

Transit and hazardous areas

LSZH and wet-location requirements under NFPA 130, and hazardous areas.

What sets Pyrotenax apart

From Chemelex's published System 1850 materials:

  • 2-hour fire-rated wiring cable for critical and essential circuits.
  • Tested to UL 2196 and ULC-S139; UL Classified and ULC Listed.
  • Listed as an Electrical Circuit Integrity System (FHIT and FHIT7) in the UL/ULC Fire Resistance Directory.
  • Meets the requirements of an Electrical Circuit Protective System referenced in NEC Articles 695 and 700.
  • Solid copper conductors, magnesium oxide insulation, seamless copper sheath; 600 V.
  • Rated 482°F continuous operating and 1850°F maximum exposure.

Codes and standards to reference

ReferenceWhat it covers
NEC Article 332Mineral-insulated, metal-sheathed cable (Type MI)
NEC Article 695Fire pumps
NEC Article 700Emergency systems
UL 2196 / ULC-S139Fire test for circuit integrity of fire-resistive power, instrumentation, control and data cables
UL FHIT / FHIT7Electrical circuit integrity systems in the UL Fire Resistance Directory
NFPA 130Fixed guideway transit and passenger rail systems

What to put in your spec

Chemelex publishes guide specification language for its MI cable systems. Key points:

  1. Rating: 2-hour fire-rated, mineral insulated cable listed in the UL Fire Resistance Directory as an electrical circuit integrity system.
  2. Complete system: cable, terminations, splices and supports installed per the listed system, not mixed components.
  3. Terminations: manufacturer termination kits (Pyropak, QuickTerm or equivalent listed kits).
  4. Circuits covered: name every circuit that needs circuit integrity, such as fire pump feeders, emergency feeders and life-safety HVAC.
  5. Testing: a system test after installation per the manufacturer's installation manual.

Check these at submittal

Fire-rated circuits only work as a listed system. Before you approve:

  • The FHIT system number covers the cable and the installation method shown.
  • Terminations and splices are part of the same listed system.
  • Support and spacing details match the listing.
  • Every circuit you identified is included in the submittal.
  • Post-installation testing is called out in the contractor's plan.
  • Any substitute is a listed 2-hour system, not a cable alone.