Spec Guide · CSI 26 05 26 · 27 05 26

Specifying Grounding Connections: nVent ERICO Cadweld

A grounding system is only as good as its connections, and most of them end up buried in earth or concrete where nobody will inspect them again. Exothermic welded connections are built for that. Here's how to specify them.

CSI sections26 05 26 · 27 05 26
StandardsUL 467 · IEEE 837
Brazill coverageNYPHILLYDC

When to specify it

Exothermic connections fit anywhere a grounding connection has to last the life of the system without maintenance.

Substations

Ground grids designed to IEEE 80, where connections are qualified to IEEE 837.

Data centers

Building grounding electrode systems, ground rings, rebar bonding and signal reference grids.

Telecom spaces

Telecom grounding busbars and bonding under 27 05 26.

Direct burial and concrete

Any connection buried in earth or encased in concrete.

What the nVent ERICO Cadweld spec requires

From nVent's published Cadweld guide specification:

  • Connections must withstand direct burial in earth or concrete without degradation over the lifetime of the grounding system.
  • Conformance to IEEE 837 for permanent substation grounding connections, with independent test data available.
  • Listed to UL 467, Grounding and Bonding Equipment.
  • Covers copper to copper, copper to steel and copper to cast iron connections.
  • Factory-controlled weld metal with batch lot numbers; molds permanently marked with manufacturer, part number and conductor size.
  • Factory-trained personnel available to train installation crews.

Codes and standards to reference

ReferenceWhat it covers
NEC Article 250Grounding and bonding
UL 467Grounding and bonding equipment
IEEE 80Safety in AC substation grounding
IEEE 837Qualifying permanent connections used in substation grounding
TIA-607-C / DTelecom grounding and bonding (busbars)

What to put in your spec

nVent publishes a Cadweld guide specification. Key points:

  1. Connection type: exothermic welded connections for all below-grade and concrete-encased grounding connections.
  2. Qualification: connections that meet IEEE 837 and are listed to UL 467, with test data submitted.
  3. Materials: molds and weld metal from the same manufacturer, marked for the conductor sizes used.
  4. Indoor work: a low-smoke exothermic process where welds are made in occupied or confined spaces.
  5. Training: installers trained by the manufacturer before work begins.
  6. Telecom: grounding busbars that meet TIA-607 in telecom rooms.

Check these at submittal

Buried connections can't be fixed later. Before you approve:

  • IEEE 837 test data is included, not just a statement.
  • UL 467 listing is shown for the connection system.
  • Molds and weld metal are from one manufacturer and sized for your conductors.
  • Compression substitutes are qualified to IEEE 837 if you'll allow them.
  • Installer training is documented.
  • Telecom busbars meet the TIA-607 edition you referenced.