Application Guide · Circuit Integrity

Keeping Critical Circuits Running in a Fire

Fire pumps, emergency power and life-safety systems are only useful if their wiring survives the fire. Code calls this circuit integrity. Here's what it means, the ways to get there, and how to specify it.

Code driversNEC 695 · 700
Fire testUL 2196
Brazill coverageNYPHILLYDC VA STATEWIDE

Circuits that typically need it

Chemelex lists these as typical uses for 2-hour fire-rated cable. Your code analysis and AHJ decide which apply to your project.

Fire pumps

Electric fire pump feeders (NEC Article 695).

Emergency systems

Emergency generators, emergency lighting and alarms (NEC Article 700).

Smoke control

Air handlers that must keep running during a fire.

Emergency elevators

Feeders to elevators that keep operating for firefighter use.

Ways to achieve circuit integrity

There are three common approaches. The right one depends on routing, space and how the rated assembly is coordinated with the architecture.

ApproachHow it worksConsiderations
Fire-resistive cable system
e.g. Pyrotenax MI
The cable itself is the 2-hour rated system, tested to UL 2196 and listed in the UL Fire Resistance Directory.Terminations, splices and supports must be part of the listed system. Routing is more flexible.
Protective system around standard wiringA listed fire-rated enclosure or wrap protects ordinary conductors and raceway.The listing has to match the exact raceway, cable and support method. Adds size and coordination.
Protection by constructionCircuits run through 2-hour rated shafts or assemblies, or are encased in concrete.Depends on architectural rated assemblies and fixed routing. Hard to change later.

What to look for in a listed cable system

From Chemelex's published Pyrotenax System 1850 materials:

  • 2-hour fire rating tested to UL 2196 and ULC-S139.
  • Listed as an electrical circuit integrity system (FHIT and FHIT7).
  • Meets the requirements of an Electrical Circuit Protective System referenced in NEC 695 and 700.
  • LSZH and wet-location compliance under NFPA 130 for transit.

Spec tips for circuit integrity

  1. List the circuits: name every feeder and branch circuit that needs a 2-hour rating, so nothing is missed at bid.
  2. Specify a listed system, including terminations, splices and supports, and the UL Fire Resistance Directory listing it must match.
  3. Call for testing after installation per the manufacturer's manual.
  4. Coordinate with the architect on rated shafts and penetrations if you mix approaches.
  5. Tell substitutes they must submit a listed 2-hour system, not a cable on its own.

Line we represent for circuit integrity

Chemelex Pyrotenax

2-hour fire-rated mineral insulated cable systems. Represented in all three territories and statewide in Virginia.

Want a second set of eyes on your spec?

Send us your draft section or project details. Our specifications team will review it and send back notes.

Product information is drawn from the manufacturer's published materials. Always confirm current listings and specifications with the manufacturer before issuing documents. Sources: Pyrotenax System 1850 · Chemelex blog: 2-hour fire-rated cable