Application Guide · Grounding & Bonding
Grounding Systems Built to Last
Data centers, substations and telecom spaces depend on a grounding system that performs for decades, mostly buried where no one will see it again. Here's what goes into one and how to specify it.
The parts of a grounding system
Grounding electrodes
Ground rods, plates and ground mats that make the connection to earth.
Ground enhancement
Ground enhancement material lowers resistance in high-resistivity soil. nVent's GEM Calculator estimates how much you need.
Permanent connections
Exothermic welded connections for buried and concrete-encased joints, qualified to IEEE 837.
Signal reference grid
A low-impedance grid under raised floors for sensitive electronic equipment.
Telecom grounding busbars
TIA-607 busbars that bond telecom equipment back to the building grounding system.
Rebar and structure bonding
Bonding kits that tie building steel and rebar into the grounding system.
What matters by facility type
| Facility | Focus | References |
|---|---|---|
| Substation | Ground grid designed for step and touch voltage; permanent connections throughout | IEEE 80, IEEE 837 |
| Data center | Grounding electrode system, ground ring, signal reference grid, telecom bonding | NEC 250, TIA-607, UL 467 |
| Telecom room | Telecom grounding busbars and bonding conductors back to the main ground | TIA-607-C / D |
Spec tips for grounding systems
- Exothermic connections below grade: specify them for every buried or concrete-encased connection.
- Ask for test data: IEEE 837 qualification and UL 467 listing for the connection system.
- Size ground enhancement from soil resistivity rather than a standard allowance.
- Name the TIA-607 edition for telecom busbars and bonding.
- Require installer training from the connection manufacturer before work begins.
Lines we represent for grounding
nVent ERICO
Grounding electrodes, GEM, Cadweld exothermic connections, signal reference grids and telecom busbars.
Champion Fiberglass
Non-conductive conduit; Champion notes grounding bushings aren't needed for protection during a cable fault.
Want a second set of eyes on your spec?
Send us your draft section or project details. Our specifications team will review it and send back notes.
Product information is drawn from the manufacturer's published materials. Always confirm current listings and specifications with the manufacturer before issuing documents. Sources: nVent ERICO Grounding and Bonding · nVent Cadweld Specification · ERICO Telecom Grounding Busbar · Champion Fiberglass Elbows